Cart

  • Cart Empty!

Every effort has been made to ensure the accuracy of all information contained herein. e-nitiative shall not be liable for any changes resulting in wrong product description, tax code and/or price. The shown information (specifications, prices, taxes) should be considered as an indication and can be changed at any moment and without any prior notice.

ADVANCE COMPUTER CENTRE LTD
59 GEORGE LANE
E18 1JJ LONDON
UK
Telephone : 02085188353
VAT : 506794623

curve_type_3_left_tcurve_type_3_right_t
Galaxy VS UPS 100kW 400V for External Batteries, Halogen-Free Cables, Marine Certified, Start-Up 5x8

Galaxy VS UPS 100kW 400V for External Batteries, Halogen-Free Cables, Marine Certified, Start-Up 5x8

£16,853.81
£20,224.57
Part Number: GVSUPS100KMHS
Language: IN
Real time Stock Check

Product Details

Introduction

Highly efficient, easy-to-deploy 100kW, 400V 3-phase UPS. Brings best-in-class power protection and low total cost of ownership to edge, small, and medium data centers, as well as critical infrastructure in commercial and industrial applications. Includes 5x8 start-up service and halogen-free cables. Marine certified.

Specifications

Main

  • Main Input Voltage : 400 V 3 phases
  • Other Input Voltage :
    • 380 V
    • 415 V
  • Main Output Voltage :400 V 3 phases
  • rated power in W : 100 kW
  • rated power in VA : 100 kVA
  • battery type
  • External battery system : Li-Ion (Lithium-Ion)
    VRLA
  • provided equipment :
    • Dust filter
    • EcoStruxure IT ready (UPS)
    • Installation guide
    • Integrated network management
    • Power modules ship installed
    • Start-up service

General

  • bypass voltage tolerance : +/- 10 %
  • redundant : No

Physical

  • colour : White
  • height : 148.5 cm
  • width : 52.1 mm
  • depth : 84.7 cm
  • net weight : 250 kg
  • USB compatible : No

Input

  • network frequency : 40...70 Hz
  • input voltage limits : 340...460 V 400 V
  • maximum input current : 180 A
  • max short time withstand current : 65 kA
  • input harmonic distortion : Less than 3 % for full load
  • load power factor : From 0.7 leading to 0.7 lagging without any derating

Output

  • Maximum configurable power in W : 50 kW
  • output frequency
    • 50 Hz sync to mains
    • 60 Hz sync to mains
    • 50 Hz +/- 0.1 % for 50 Hz nominal unsynchronised
    • 60 Hz +/- 0.1 % for 60 Hz nominal unsynchronised
  • crest factor :2.5
  • Wave type : Sine wave
  • output voltage tolerance :+/-1% after 50ms
  • output harmonic distortion : < 1% linear load and < 5% non-linear load
  • output overload operation : 10 minutes at 125% and 60 seconds at 150%
  • bypass type : Built-in static bypass
  • Maximum configurable power in VA : 100 kVA

Conformance

  • standards
    • EN/IEC 62040-1
    • EN/IEC 62040-2
    • FCC part 15 class A
    • IEC 60721-4-2 level 2M2
    • UL 1778 5th edition

Environmental

  • ambient air temperature for operation : 0…40 °C
  • relative humidity : 0…95 % non-condensing
  • operating altitude : 0...3300 ft
  • ambient air temperature for storage : -25…55 °C
  • storage Relative Humidity : 10…80 % Non-condensing
  • acoustic level : 68 dBA
  • heat dissipation : 5804 Btu/h
  • IP degree of protection : IP21

Batteries & Runtime

  • battery voltage : 480...576 V DC
  • discharge battery voltage : 384 V DC
  • max current discharge : 271 A
  • Battery power in VAH : 0 VAh runtime
  • extended runtime :0

Communications & Management

  • control panel: Touch screen LCD user interface
  • alarm : Audible and visible alarms prioritized by severity