Every effort has been made to ensure the accuracy of all information contained herein. e-nitiative shall not be liable for any changes resulting in wrong product description, tax code and/or price. The shown information (specifications, prices, taxes) should be considered as an indication and can be changed at any moment and without any prior notice.
ADVANCE COMPUTER CENTRE LTD
59 GEORGE LANE
E18 1JJ LONDON
UK
Telephone : 02085188353
VAT : 506794623
Part Number: | G35T20KH4B4S |
Language: | IN |
APC MGE Galaxy 3500, 16 kW / 20 kVA,Input 400V 3PH / Output 400V 3PH, Extended runtime model.
Includes: Battery modules ship installed, Bolt down brackets, CD with software, Installation guide, Network Management Card, Power modules ship installed, Smart UPS signalling RS-232 cable, Start-Up Service, User Manual.
- Dual mains input
Increases availability by allowing the UPS to be connected to two separate power sources.
- Generator compatible
Ensures clean, uninterrupted power to protected equipment when generator power is used.
- Parallel-redundant capable
Power the connected equipment with multiple UPSs to increase system redundancy
Availability
- Dual mains input
Increases availability by allowing the UPS to be connected to two separate power sources.
- Hot-swappable batteries
Ensures clean, uninterrupted power to protected equipment while batteries are being replaced
- Parallel-capacity capable
Increases total power capacity by using multiple UPSs simultaneously.
- Advanced electrical features
Excellent power conditioning, very low harmonic distortion through IGBT rectifier, input power factor correction, and high efficiency
- Frequency and voltage regulation
Gives higher application availability by correcting poor frequency and voltage conditions without using the battery.
- Automatic internal bypass
Supplies utility power to the connected loads in the event of a UPS overload condition or fault.
- Generator compatible
Ensures clean, uninterrupted power to protected equipment when generator power is used.
Manageability
- Built-in Web/SNMP management
Full-featured management via a Web browser as well as comprehensive management from a Network Management System.
- Environmental Monitoring
Prevent equipment failure from a full range of threatening environmental conditions.
- LCD graphics display
Text and mimic diagrams that display modes of operation, system parameters and alarms.
- Audible alarms
Provides notification of changing utility power and UPS conditions.
20 kVA
16000 W
40/70 Hz
27 A
Y
51.3 dB
Sealed Lead Acid (VRLA)
5 h
2
Black
CE,EN 50091-2,EN/IEC 62040-3,EN/IEC 62040-1-1,IEC 61000-3-2,IEC 61000-3-3,ISO 14001,ISO 9001,VFI-SS-111
0 - 40 °C
-15 - 45 °C
0 - 95%
0 - 95%
0 - 999.9 m
0 - 15000 m
443 kg
474 kg
VRLA
1 x 4-wire (3PH + G) 1 x 5-wire (3PH + N + G) 1 x Screw Terminals
5-wire (3PH + N + G)
523 x 838 x 1491 mm
+/-1%, +/- 5%
650 x 1062 x 1643 mm